声波法直埋热水供热管道泄漏检测定位
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

TU995.3

基金项目:

北京市热力集团合作项目(KY191007);北京学者计划资助项目(2015NO.022)


Research on Leakage Detection and Localization of Direct Buried Hot Water Heating Pipeline by Acoustic Wave Method
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    为快速诊断供热管网泄漏,提升供热管网运行安全,搭建了供热管道泄漏检测与定位的试验台,采用加速度传感器进行声波测量,研究供热管道不同运行压力、温度、泄漏孔径、漏点位置等对供热管道泄漏声波特性与漏点定位的影响。结果表明:供热管道未泄漏时背景噪声能量集中在0~1000Hz,泄漏后的声波能量集中在1200~2400Hz和3200~4000Hz范围。管内压力和泄漏孔径增大后,泄漏声波信号幅值增大,信号能量增强,高频段能量占比增加,漏点定位精度提高;而温度升高后,泄漏声波信号幅值减小,信号能量减弱,低频段能量占比增加,漏点定位精度下降;漏点相对位置对漏点定位精度影响小,带通滤波处理后,漏点定位精度明显提高。

    Abstract:

    In order to quickly diagnose the leakage of heating pipe network and improve its operation safety, a test apparatus for leakage detection and localization of heating pipe was built, and the acceleration sensors were used to measure the acoustic waves,the influence of different operation pressure, temperature, leakage aperture and leakage point location on leakage acoustic wave characteristics and leakage localization of heating pipeline were studied. The results indicate that when there is no leakage in heating pipe, the background noise energy is concentrated in the range of 0-1000Hz, after leakage occurs, the acoustic energy due to leaking will be concentrated in the range of 1200-2400Hz and 3200-4000Hz. With the increase of pressure and leakage aperture, the amplitude of leakage acoustic signal increases, the signal energy increases, the proportion of high frequency band energy increases, and the leakage localization becomes accurate; however, with the temperature increase, the amplitude of leakage acoustic signal decreases, the signal energy decreases, the proportion of low frequency band energy increases, and the leakage localization gets worse, the relative position of leakage point has little influence on the leakage localization accuracy, the approach by bandpass filtering could significantly improve the accuracy.

    参考文献
    相似文献
    引证文献
引用本文

郭帅杰,张立申,李成,等. 声波法直埋热水供热管道泄漏检测定位[J]. 科学技术与工程, 2023, 23(11): 4765-4772.
Guo Shuaijie, Zhang Lishen, Li Cheng, et al. Research on Leakage Detection and Localization of Direct Buried Hot Water Heating Pipeline by Acoustic Wave Method[J]. Science Technology and Engineering,2023,23(11):4765-4772.

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2022-08-18
  • 最后修改日期:2023-02-13
  • 录用日期:2022-11-29
  • 在线发布日期: 2023-05-10
  • 出版日期:
×
律回春渐,新元肇启|《科学技术与工程》编辑部恭祝新岁!
亟待确认版面费归属稿件,敬请作者关注