Voltage and Reactive Power Control Strategy with the Presence of Multiple Distribution Generations
Author:
Affiliation:

College of Automation Engineering, Shanghai University of Electric Power,College of Automation Engineering,Shanghai University of Electric Power,Shanghai ,China,College of Automation Engineering,Shanghai University of Electric Power,Shanghai ,China,Shanghai Minghua Power Technology Engineering CO,LTD,Shanghai ,China

Fund Project:

Shanghai Science and Technology Commission Program (16DZ1202500 and 15111106800)

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    针对负荷的时变性和DG出力的波动性使得基于实时无功优化的电压控制效果劣化问题,提出了一种含多DG的配电网电压无功优化控制策略,推导了负荷节点注入无功功率对电压变化的灵敏度矩阵,给出了SCB投切组数的确定方法,基于改进递推贝叶斯估计方法估算最佳的OLTC,利用RTU所获取的相关数据确定各馈线处SVR的分接头开关档位,根据目标值调整控制变量实行自主优化选择和投切控制,达到最优控制方式。以加入多种DG和负荷类型的IEEE33节点典型馈线系统作为仿真算例,分析结果表明所提控制策略能显著地稳定电压幅值,具有较好的在线应用前景。

    Abstract:

    The time-varying of load and stochastic variability of distribution generation (DG) deteriorate the voltage control based on real-time reactive power optimization. Voltage and reactive power control strategy for distribution network with the presence of multiple DGs is presented in this paper to address the above issue. The nodes’ reactive power injections was deduced based on the voltage deviation of real-time detection and the sensitivity matrix of reactive power to voltage deviation, so that the shunt capacitor bank set number can be determined. Optimum transformer tap position is estimated by improved recursive Bayesian approach. The optimum step voltage regulator position is calculated based on the Remote Terminal Unit (RTU) data which are collected from the selected points of distribution feeders. And next moment the control center adjusts the control variables according to a target value which guarantees the real-time character. Simulations are carried on the 33-bus IEEE test system to illustrate that the approach is reliable and with high efficiency, it is also well fit for on-line application.

    参考文献
    相似文献
    引证文献
引用本文

彭道刚,王亮,钱玉良,等. 计及多类型分布式电源的电压无功优化控制研究[J]. 科学技术与工程, 2017, 17(13): .
PENG Daogang, WANG Liang, QIAN Yuliang, et al. Voltage and Reactive Power Control Strategy with the Presence of Multiple Distribution Generations[J]. Science Technology and Engineering,2017,17(13).

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2016-10-10
  • 最后修改日期:2016-12-07
  • 录用日期:2016-12-15
  • 在线发布日期: 2017-05-22
  • 出版日期:
×
律回春渐,新元肇启|《科学技术与工程》编辑部恭祝新岁!
亟待确认版面费归属稿件,敬请作者关注