首页|期刊简介|投稿指南|分类索引|刊文选读|订阅指南|证明资料|样刊邮寄查询|常见问题解答|联系我们
胡安平,陶以彬,庄俊,等. 基于扰动无功功率的电压暂降源定位[J]. 科学技术与工程, 2020, 20(30): 12415-12422.
Hu Anping,et al.Voltage sag location based on disturbance reactive powerHU An-ping1, 2, TAO Yi-bin1, 2, YANG Bo1, 2, QU Ke3, LI Guan-jun1, 2, DING Kai4[J].Science Technology and Engineering,2020,20(30):12415-12422.
基于扰动无功功率的电压暂降源定位
Voltage sag location based on disturbance reactive powerHU An-ping1, 2, TAO Yi-bin1, 2, YANG Bo1, 2, QU Ke3, LI Guan-jun1, 2, DING Kai4
投稿时间:2019-08-26  修订日期:2020-07-31
DOI:
中文关键词:  电压暂降  定位  扰动  无功功率  负序
英文关键词:
基金项目:国家电网公司总部科技项目(现代工业园区电压暂降影响因素评估及防治关键技术研究:NY71-18-027)
                 
作者单位
胡安平 新能源与储能运行控制国家重点实验室
陶以彬 江苏省储能变流及应用工程技术研究中心
庄俊 新能源与储能运行控制国家重点实验室
瞿科 四川大学电气工程学院
胡畔 国网湖北省电力有限公司电力科学研究院
丁凯 国网湖北省电力有限公司电力科学研究院
摘要点击次数: 115
全文下载次数: 52
中文摘要:
      暂降源定位对于查找暂降源、划分暂降责任有重要作用。为了确定暂降源的上下游位置,本文从线性电路的叠加原理入手,通过分析故障过程中电气特征变化规律,提出了基于扰动无功功率变化特征的电压暂降源定位方法。当发生三相对称故障时,如果监测点的正序扰动无功功率方向与规定正方向一致,电压暂降源在上游,反之则在下游;当发生不对称故障时,如果监测点的负序扰动无功功率方向与规定正方向一致,电压暂降源在下游,反之则在上游。大量仿真与实测数据表明,本文方法不受暂降持续时间影响,能够实现电压暂降源的上下游定位,具有较高准确率。
英文摘要:
      Voltage sag location plays a significant role in seeking voltage sag source and dividing responsibility. In order to determine the location of a voltage sag source, based on the superposition principle of linear circuit and through analyzing the change rules of electrical characteristics during faults, a voltage sag location approach is proposed on the basis of change features of disturbance reactive power. When a three-phase symmetric fault occurs, the voltage sag source is determined in the upstream if the direction of positive-sequence disturbance reactive power is in accord with the regulated positive direction at a monitoring point, otherwise, in the downstream. When an asymmetric fault occurs, the voltage sag source is determined in the downstream if the direction of negative-sequence disturbance reactive power is in accord with the regulated positive direction at a monitoring point, otherwise, in the upstream. A large quantity of simulation and measured data indicates the proposed approach is not susceptible to sag duration and can make it possible to determine the upstream or downstream location of a voltage sag source. The approach has high accuracy of location.